-Airconditioner Installation Accessories-
Google伕打﹋↓伉件弁﹌
TOP > Products > Insulated Copper Tube & Fittings Index > FLARE NUT and FLARE COUPLER

FN/FUN - FLARE NUT and FLARE COUPLER -

update: 2013-11-20
image1.jpg image2.jpg image3.jpg
"FN" FLARE NUT "UN" FLARE COUPLER "FUN" FLARE COUPLER
with Flare Nut
head of this page

Lineup

"FN" FLARE NUT

Code No.Item No.Applicable copper tube sizePcs/Pkg(pcs*bag)
10082 FN-2B 6.35(1/4) 100(10*10)
10083 FN-3B 9.35(3/8) 100(10*10)
10084 FN-4B 12.70(1/2) 100(10*10)
10085 FN-5B 15.88(5/8) 100(10*10)
10086 FN-6B 19.05(3/4) 100(10*10)


"UN" FLARE COUPLER

Code No.Item No.Applicable copper tube sizePcs/Pkg(pcs*bag)
10102 UN-2B 6.35(1/4) 50(5*10)
10103 UN-3B 9.52(3/8) 50(5*10)
10104 UN-4B 12.70(1/2) 50(5*10)
10105 UN-5B 15.88(5/8) 50(5*10)
10106 UN-6B 19.05(3/4) 50(5*10)


"FUN" FLARE COUPLER with Flare Nut

Code No.Item No.Applicable copper tube sizePcs/Pkg(pcs*bag)
10092 FUN-2B 6.35(1/4) 100(10*10)
10093 FUN-3B 9.52(3/8) 100(10*10)
10094 FUN-4B 12.70(1/2) 100(10*10)
10095 FUN-5B 15.88(5/8) 100(10*10)
10096 FUN-6B 19.05(3/4) 50(5*10)


head of this page

Specification

ItemValue
Applicable refrigerant R410A. R407C. R134a. R404A. R507A. R22


head of this page

Caution

  • Nuts must be tightened with a torque wrench strictly to torque specifications listed in the table below.
    Overtightening will cause stress corrosion cracks on the flare nut and undertightening will lead to refrigerant leakage.
Standard Torque Specifications for Flare Nuts :
Nominal diameter1/43/81/25/83/4
Torque(N•m) 16±2 38±4 55±6 75±7 110±10